Emerson Liebert.PEX+ Series User Manual page 50

Precision air conditioner
Hide thumbs Also See for Liebert.PEX+ Series:
Table of Contents

Advertisement

42
Chapter 5 iCOM Controller
Types
C-In2
Customized alarm 2
C-In3
Customized alarm 3
C-In4
Customized alarm 4
RHT
Reheater lockout
HUM
Humidifier lockout
C1 ACT, C2 ACT, C3 ACT and C4 ACT correspond to the customer alarms. 'OPEN' means normally open, 'CLOSE'
means normally closed.
Alarm delays setting
The alarm delays are the time after faults occur and before the alarms are triggered. See Figure 5-10 for the menu
format.
The alarm name, delay time, delay enabling and alarm type are displayed from left to right in the list.
The alarm delay can be set to 0 ~ 9999. Unit: second.
The delay enabling determines whether the alarm will be displayed and the alarm menu is entered, Options include
'Yes' and 'No'.
The alarm type can be set to 'ALM' (alarm), 'WRN' (warning) and 'MSG' (message). They determine the alarm degree
of the corresponding event.
The alarm names are listed in Table 5-26.
Alarm/event
SN
name
S236
FOL
S237
LOA
S238
CF
S239
HRT
S240
LRT
S241
HRH
S242
LRH
S243
HTA
S244
LTA
S245
HHA
S246
LHA
S249
OL1
S250
OL2
S251
HP1
S252
HP2
S253
LP1
S254
LP2
S255
PD1
S256
PD2
S257
HT1
S258
HT2
S259
EHO
S262
WHE
S263
SMO
S264
WUF
S265
CPH
Description
Types
FLOSD
FLOLC
ComPD
En FC
RJVFD
SET ALARMS
S236
S237
S238
S239
S240
S241
Table 5-26 Alarm name description
Description
Fan overload
Loss of airflow
Filter clogged
High room temp.
Low room temp.
High room hum.
Low room hum.
High temperature of sensor A
Low temperature of sensor A
High humidity of sensor A
Low humidity of sensor A
Compressor 1 overload
Compressor 2 overload
Compressor 1 high pressure
Compressor 2 high pressure
Compressor 1 low pressure
Compressor 2 low pressure
Compressor 1 pumpdown fails
Compressor 2 pumpdown fails
Digital scroll 1 high temperature
Digital scroll 2 high temperature
EL HEAT HIGH TEMP
Working hours exceeded
Smoke detected
Water under floor
Conderser pump high water
Liebert. PEX+Series Precision Air Conditioner
Description
Flow AL SD
Flow AL LC
Comp Lock PD
Enable FC,
HTRJ VFD
2/10
01
T
DEL
EN
FOL
5
Yes
ALM
3
Yes
ALM
LOA
2
Yes
WRN
CF
Yes
WRN
HRT
30
Yes
LRT
30
WRN
30
Yes
HRH
WRN
Figure 5-10
Alarm delay
SN
S266
S267
S268
S269
S270
S271
S272
S275
S276
S277
S278
S279
S280
S281
S282
S283
S284
S285
S288
S289
S290
S291
S292
S293
S294
S295
Types
ScRed
D-Scroll Red
Swap V
Swap Valve
ECFan
EC Fan Fail
Alarm/event
name
LOF
Loss of flow
SGP
Standby glycol pump on
STB
Standby unit on
HUP
Humidifier problem
NOC
No connection w/Unit1
-
No connection w/UnitX
LOP
LOSS OF POWER
CI1
CUSTOMER INPUT 1
CI2
CUSTOMER INPUT 2
CI3
Customized input 3
CI4
Customized input 4
CS
Call for service
HTD
High temperature
LB1
Loss of air blower 2
RL
Reheat lockout
HL
Humidifier lockout
FCL
FC lockout
CL
Compressor(s) lockout
SC1
Short cycle 1
SC2
Short cycle 2
NOP
NO power
CN1
Condensor 1 Fail
CN2
Condensor 2 Fail
EFF
EC Fan fail
HST
High supply air temperature
LST
Low supply air temperature