A.8

Sensor characteristics

Table A- 16
Sensor characteristics, MAG 6000
MODBUS
MODBUS
register
address
4:02401
2400
4:02403
2402
4:02405
2404
4:02421
2420
Table A- 17
Sensor characteristics, MASS 6000
MODBUS
MODBUS
register
address
4:02401
2400
4:02403
2402
4:02405
2404
4:02407
2406
4:02409
2408
4:02411
2410
4:02413
2412
4:02415
2414
4:02417
2416
4:02419
2418
4:02422
2421
Modbus RTU RS485
Operating Instructions, 06/2010, A5E00753974-04
No. of bytes Data type
4
Float
4
Float
4
Float
2
Byte
No. of bytes Data type
4
Float
4
Float
4
Float
4
Float
4
Float
4
Float
4
Float
4
Float
4
Float
4
Float
4
Float
Description
Sensor size (m)
Calibration factor
Correction factor
Excitation frequency:
0 = 3.125 Hz (50 Hz)
1 = 6.25 Hz (50 Hz)
2 = 12.5 Hz (50 Hz)
3 = 25 Hz (50 Hz)
4 = 1.5625 Hz (50 Hz)
5 = 44 Hz (only SV)
6 = 2.0833 Hz
7 = 1.875 Hz (60 Hz)
8 = 3.75 Hz (60 Hz)
9 = 7.5 Hz (60 Hz)
10 = 15 Hz (60 Hz)
11 = 30 Hz (60 Hz)
Description
Sensor size (m)
Calibration factor (us2/kg)
Correction factor
Sensor TC (1/100% / °C)
Density parm. A (kg/m3)
Density parm. B (*10E6)
Density TC (1/100% / °C)
Density offset (kg/m3)
Density factor
Table slope (kg/s)
Fraction offset (kg/s)
Modbus holding registers
A.8 Sensor characteristics
Read / write
R/W
R/W
R/W
R/W
Read / write
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
51