7.2.1
Sensor (2.2.)
7.2.1.1
Units (2.2.1.)
Description
Options
Factory setting
7.2.1.2
Sensor mode (2.2.2.)
①
②
③
④
Mode
NO SERVICE
LEVEL
(factory setting)
SPACE
DISTANCE
For more detail, refer to Material level (2.5.1.) (Page 103).
1)
7.2.1.3
Material (2.2.3.)
Description
Options
Factory setting
Related
parameters
dK < 3.0
1)
SITRANS LR200 with mA/HART
Operating Instructions, 05/2019, A5E32337676-AE
sensor measurement units
m, cm, mm, ft, in
m
Sensor value
Space
Distance
High calibration point
Description
Measurement and associated loop
current are not updated, and the
device defaults to Fail-safe mode
Distance to material surface
Automatically configures the device to operate in the chosen application type, by
changing one or more of the following parameters: Propagation Factor, Position
Detect, and/or CLEF Range.
LIQUID
LIQUID LOW DK
LIQUID
Propagation factor (2.8.3.) (Page 111)
Position detect (2.8.4.2.) (Page 112)
CLEF range (2.8.4.4.) (Page 112)
⑤
Low calibration point
⑥
Far range
⑦
Level
.
1)
(low dielectric liquid - CLEF algorithm enabled
1)
Reference point
N/A
Low Calibration Point (process empty
level)
High Calibration Point (process full level)
Sensor Reference Point
99