Installing the controller

Wiring sensors to the controller

You can connect the following sensors:
Leaving chilled water header temperature (required)
Outdoor air temperature (optional)
Relative humidity (optional)
NOTE This document gives instructions for wiring the sensors to the controller. For mounting and wiring the
sensors, see the Carrier Sensors Installation Guide.
WARNING Disconnect electrical power to the controller before wiring it. Failure to follow this warning could
cause electrical shock, personal injury, or damage to the controller.
CAUTIONS
Do not run sensor or relay wires in the same conduit or raceway with Class 1 AC or DC service wiring.
Do not abrade, cut, or nick the outer jacket of the cable.
Do not pull or draw cable with a force that may harm the physical or electrical properties.
Avoid splices in any control wiring.

Wiring specifications

Cable from sensor to controller:
Maximum length:

To wire the leaving chilled water header temperature sensor to the controller

Use one of the following leaving chilled water header 5k Ohm temperature sensors with associated immersion
well:
5k Ohm thermistor
HH79NZ014
HH79NZ029
30MP Multi-chiller
Installation and Start-up Guide
If <100 ft (30.5 meters)
If >100 ft (30.5 meters)
500 feet (152 meters)
Size
Immersion Well
3 in.
10HB50106801
4 in.
10HB50106802
12
22 AWG, unshielded
22 AWG, shielded
CARRIER CORPORATION ©2018
All rights reserved