The leaving chilled water header temperature sensor is required and used to measure the temperature of the
water in the common supply header leaving the chillers.
1
Strip the outer jacket from the cable for at least 4 inches (10.2 cm). Strip .25 inch (.6 cm) of insulation from
each wire.
2
Wire the sensor to the controller. See diagram below.
3
Sensor may be terminated at Input 4.
4
Apply power and verify sensor readings.
To wire an outdoor air temperature sensor to the controller
Part #33ZCSENOAT
You can use an optional outdoor air temperature (OAT) sensor to provide a reset of the chilled water setpoint
adjustment based on the OAT reset.
1
Strip the outer jacket from the cable for at least 4 inches (10.2 cm). Strip .25 inch (.6 cm) of insulation from
each wire.
2
Wire the sensor to the controller. See diagram below.
3
Sensor may be terminated at Input 3.
30MP Multi-chiller
Installation and Start-up Guide
13