Setpoints - Carrier 30MP Installation And Startup Manual

Multi-chiller
Table of Contents

Advertisement

Point Name/Description
Defined Time for Rotation – Specify the time of day (24 hour format) for automatic
rotation based on the method and schedule you selected.
(Not applicable to Runtime Equalization.)
Runtime Since Last Rotation
Chiller
Runtime
CH-1
0.0 hr
CH-2
0.0 hr
Chiller Order
Chiller
Position
CH-1
1
CH-2
0

Setpoints

Navigation:
i-Vu® / Field Assistant:
Point Name/Description
Chilled Water Setpoint - The chilled water temperature setpoint maintained by the chiller
plant. The setpoint is internally clamped so it will not exceed the highest freeze point
configured in any chiller.
Condenser Water Temperature
CW Min Load Setpoint – The condenser water temperature setpoint at minimum load.
CW Part Load Setpoint – The condenser water temperature setpoint at partial load.
CW Full Load Setpoint – The condenser water temperature setpoint at full load.
30MP Multi-chiller
Installation and Start-up Guide
Properties
Control Program
>
35
Appendix C: 30MP Multi-chiller Points/Properties
Range
D:
8:00
R:
1:00 to 24:00
R:
_hrs
R
1 to 8
0 = not available
Configuration
Setpoints
>
>
Range
D:
44°F
R:
40 to 80°F for water
-20 to 45°F for brine
D:
65°F
R:
50 to 85°F
D:
70°F
R:
50 to 85°F
D:
76°F
R:
50 to 85°F
CARRIER CORPORATION ©2018
All rights reserved