FULTON J Series Installation, Operation, Maintenance And Parts Manual page 47

Oil fired steam boilers
Table of Contents

Advertisement

5
It is very important that a strict water management program is followed
pH Value
Hardness
Suspended Solids
Chloride
Organic Matter
Oil
pH Value
Hardness
Suspended Solids
Chloride
Oxygen Scavenger,
Sodium Sulphite or Tannin
Phosphate
Total Alkalinity
Caustic Alkalinity
Total Dissolved Solids (TDS)
Iron
Silica
Dissolved Oxygen
mg/kg
CaCO
3
PO
4
SiO
2
1 grain hardness
therefore 70ppm
For practical purposes mg/kg
It is critical that the boiler water pH be alkaline (9.5 - 11.5) whenever water is in the boiler.
Daily boiler blowdown is essential to help prevent formation of deposits and reduce
Total Dissolved Solids (TDS).
Consult your Water Treatment specialist to establish the frequency and duration
of blowdown required to achieve the required water conditions.
Recommended Water Conditions
to ensure trouble free boiler operation.
The following are recommended for feedwater and boiler water.
FEEDWATER
BOILER WATER
IMPORTANT
(water entering boiler)
8.5 to 9.5 tested at room temperature,
less than 2.0 mg/kg in the form of CaCO
None
Less than 50 mg/kg
Less than 5 mg/kg
None
(water inside boiler)
9.5 - 11.5, tested at room temperature
Not detectable
Less than 100 mg/kg
Less than 500 mg/kg
20 to 50mg/kg
Less than 50 mg/kg, in the form of PO
Less than 1000 mg/kg
Less than 300 mg/kg as CaCO
Less than 2000 ppm
Less than 1 mg/kg
Less than 150 mg/kg, in the form of SiO
None
=
Milligrams per Kilogram
=
Calcium Carbonate
=
Phosphate
=
Silica
=
17.118 ppm
=
4.10 grains hardness.
=
ppm
J OIL-E-08 2008
5
,
3
4
3
2
42

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

6j8j10j15j20j30j ... Show all