TROUBLESHOOTINg - continued.
Problem
Boiler is Surging
Boiler Rumbles
Boiler pushing
water with steam
Pump will
not cutoff
Pump runs but
does not put
water in the boiler
Water pump runs
intermittently
Boiler contiues
after shut down
Oil fumes coming
out around the oil
pump housing
on shut down
Boiler flooding
29
Cause
1. Steam Traps
blowing through.
2. Scale buildup or
lime deposits.
3. Too much water
treatment.
4. Too much of a load.
1. Draft Problem
2. Too much main air.
3. Air or water in the oil.
1. Steam Traps
2. Too much water
treatment.
1. Dirty Probes.
2. Relay failed.
3. Earth connection.
1. Vapour locking
of pump.
2. Blocked feed water line
1. Scale on probes.
2. Bad pump contactor.
3. Pump Motor damaged.
1. Oil Valve defective
1. Bad draft condition
2. Venting of room
1. Pump does not shut off.
2. Relay failed.
3. Earth connection.
4. Vacuum created
with the boiler off.
J OIL-E-08 2008
Remedy
Check traps, clean or replace as required.
Call water treatment company and consult
the factory.
Dump the return tank and flush the system.
Test the water treatment.
Check total equipment load against the boiler
output. Decrease amount of equipment being
used.
Check draft is neutral. Consider installing a
barometric damper if the draft is too strong.
Adjust main air.
Check tank and lines for water or leaks.
Check traps. Clean or replace as required.
Dump the return tank and flush the system.
Test the water treatment.
Clean or replace as required.
Check relay is secure on its base, if so
replace the relay.
Check for tightness and clean.
Allow system to cool down, check steam traps
and check to be sure return lines are not
insulated. Check return tank temperature, if it is
above 82
C vapour locking of the pump will
O
occur. Inspect check valves. Clean and replace
as needed. Replace pump with multi-stage
centrifugal pump able to cope with 121
Check feed water line is not blocked, clean as
required.
Check probes, clean as required.
Check to ensure the contactor is live.
Check to ensure the contactor coil is being
pulled in. Replace as required.
Check the pump circuit is live. If the circuit is live
but the pump is not running, replace the pump.
Check the valve is opening and closing.
Clean or replace as required.
Check the draft with a gauge, should read neutral.
May need to install a barometric damper.
Ensure the boiler room doors are closed and the
recommended vents are clear.
Dirty probes, clean or replace as required.
Check relay is secure on its base, if so
replace the relay.
Check for tightness and clean.
As the boiler cools it pulls water from the system.
To prevent this, add an anti-vacuum valve on the
steam gauge assembly piping, this valve closes
under pressure and opens under vacuum.