Evoqua WALLACE & TIERNAN SFC fieldbus Manual page 56

Module retrofit set
Table of Contents

Advertisement

Available languages

Available languages

3.
Description
Modbus
IN-
OUT-
Name
Register
byte
byte
40019 36
Relays OUT/Digital IN
40020 38
Operation Mode
40021 40
Error code
40023 44 0
Setpoint
40025 48 4
Dosing factor
40027 52 8
Xp
40028 54 10
Tn
40030 58 14
Ymin
40032 62 18
Ymax
40034 66 22
Limit high (1)
40036 70 26
Limit low (1)
40038 74 30
Limit high (2)
40040 78 34
Limit low (2)
56
SFC fieldbus module retrofit set
Format
Length
Access
2
UINT16 R
0x0001 - Alarm relay 1
0x0002 - Alarm relay 2
0x0004 - Alarm relay 3
0x0008 - Alarm relay 4
0x0010 - not defined
...
0x0080 - n.d.
0x0100 - Digital input 1
0x0200 - Digital input 2
0x0400 - n.d.
...
0x8000 - n.d.
2
UINT16 R
0x0001 - Automatic
0x0002 - Manual
0x0004 - Adaptive control
0x0008 - Stop controller
0x0010 - Ratio mode
0x0020 - Constant mode
0x0040 - Combined mode
0x0080 - Sample line dosing
4
ULON
R
0x00000001 - Error - Zero point
G
0x00000002 - Error - Calibration
0x00000004 - Error - Cell
0x00000008 - Error - Measuring range
0x00000010 - Error - Setpoint
0x00000020 - Error - CAN-measured value
0x00000040 - Error - Load mA-Output
0x00000080 - Error - Positioner Ym
0x00000100 - Error - Positioner calibration
0x00000200 - Error - mA-Input 1 (Wq)
0x00000400 - Error - mA-Input 2 (We/De)
0x00000800 - Error - Adaption
0x00001000 - Error - HOCL
0x00002000 - Error - Combined chlorine measurement
0x00004000 - Error - Temperature (Multi Sensor)
0x00008000 - Error - Temperature (measuring module)
0x00010000 - Error - Modul
0x00020000 - Error - CAN-actuator
0x40000000 - Feedback - Sample-Wash
0x80000000 - Feedback - Sample water inlet desinfection
4
FLOAT R/W
4
FLOAT R/W
2
UINT16 R/W
4
FLOAT R/W
4
FLOAT R/W
4
FLOAT R/W
4
FLOAT R/W
4
FLOAT R/W
4
FLOAT R/W
4
FLOAT R/W
Description