Relative Humidity Operation
Relative Humidity Sensor
The thermostat includes an internal relative humidity (RH) sensor and has the option to connect to an
external RH sensor . The installer has the option to disable the internal RH sensor when an external
RH sensor is installed . When both the internal and external RH sensors are enabled, the RH reading
is averaged .
Humidifier Operation
The thermostat controls the relative humidity (RH) by operating either the Accessory 1 or Accessory 2
relays . This is an installer configurable setting . When the RH is below the Humidify To setting by 3%,
the Accessory 1 or 2 relay is closed to operate a humidifier . The humidifier is shut off when the RH
reaches the Humidify To setting .
The thermostat can operate 3 types of humidifiers:
Stand Alone
- The humidifier is not connected to the HVAC system .
- The thermostat Mode can be set to Heat, Cool, Auto or Off .
Steam
- The steam humidifier is ducted to the HVAC system .
- The thermostat Mode can be set to Heat, Cool, Auto or Off .
- Requires the system fan to turn on when operating .
Evaporative
- A drum style humidifier which requires the heating system to operate
to evaporate the water .
- This system requires the system fan to operate .
- The thermostat Mode must be set to Heat or Auto .
Humidifier Window Protection
During cold weather, condensation will form on windows when the relative humidity (RH) is too high .
The optional window protection feature automatically calculates the indoor dew point based upon
the outdoor temperature and the quality of the windows installed . The humidifier is then operated to
the highest possible RH that is below the Humidify To setting . This feature requires a wired outdoor
sensor to be installed .
Dehumidifier Operation
The thermostat controls the relative humidity (RH) by operating either the Accessory 1 or Accessory 2
relay . This is an installer configurable setting . When the RH is above the Dehumidify To setting by 3%,
the Accessory 1 or 2 relay is closed to operate the dehumidifier . The dehumidifier is shut off when the
RH reaches the Dehumidify To setting .
The thermostat can operate 2 types of dehumidifiers:
Stand Alone
- The dehumidifier is not connected to the HVAC system .
- The thermostat Mode can be set to Heat, Cool, Auto or Off .
DX Coil
- The HVAC cooling system is used for dehumidification .
- The Accessory 1 or Accessory 2 relay activates the DHUM operation on the air
handling unit to operate the system fan at low speed .
- The cooling compressor Y1 and Y2 relays are operated . The chilled DX coil
condenses moisture from the air .
- The cooling system can over cool the room temperature by 2°F (1°C) during
dehumidification .