5.9
Burner closing
Once the combustion head adjustment is completed:
reassemble the burner on the guides 3) at about 100 mm
from the pipe coupling 4) - burner in the position shown in
Fig. 16;
insert the probe and electrode cables, then slide the burner
as far as the pipe coupling - burner in the position shown in
Fig. 19;
20156417
Installation
connect the socket of the maximum gas pressure switch;
refit the screws 2) on the guides 3);
fix the burner to the pipe coupling with the screws 1).
WARNING
2
3
4
20113906
24
GB
When fitting the burner on the two guides, it is
advisable to gently draw out the high voltage
cable and flame detection probe cable until they
are slightly taut.
5
1
Fig. 19