Stopping Of The Burner; Final Checks (With Burner Operating) - Riello RS 160/EV O2 BLU Installation, Use And Maintenance Instructions

Forced draught gas burners
Table of Contents

Advertisement

6.9

Stopping of the burner

The burner can be stopped by:
 intervening on the disconnecting switch of the electrical sup-
ply line, located on the boiler panel;
 working on the switch " 0-AUTO " of Fig. 30 at page 31;
 removing the transparent protection that covers the Operator
Panel.
6.10

Final checks (with burner operating)

 Open the thermostat/pressure switch TL
 Open the thermostat/pressure switch TS
 Turn the gas maximum pressure switch knob to the mini-
mum end of scale position
 Turn the air pressure switch to the maximum end of scale
position.
 Disconnect the minimum gas pressure switch connector.
 Disconnect the ionisation probe wire
Make sure that the mechanical locking systems
on the various adjustment devices are fully tight-
ened.
WARNING
20156417
Start-up, calibration and operation of the burner
The burner must stop
The burner must stop in lockout
The burner must not start
The burner must stop in lockout due to firing failure
34