6.5.3

Minimum gas pressure switch

Adjust the minimum gas pressure switch (Fig. 33) after having
performed all other burner adjustments with the pressure switch
set to the start of the scale.
With the burner operating at maximum output, increase adjust-
ment pressure by slowly turning the relative knob clockwise until
the burner locks out.
Then turn the knob anticlockwise by 0.2 kPa (2 mbar) and repeat
the burner start-up to ensure it is regular.
If the burner locks out again, turn the knob anticlockwise again by
0.1 kPa (1 mbar)
6.5.4

PVP pressure switch kit

Adjust the pressure switch for the valve leak detection control de-
vice (PVP Kit)(Fig. 34), if present, according to the instructions
supplied with the Kit itself.
1 kPa = 10 mbar
WARNING
6.6

Steady-state operation

Once the start-up cycle is completed, the servomotor command
moves on to the thermostat/pressure switch that controls the
pressure or the temperature in the boiler.
 If the temperature or the pressure is low the burner progres-
sively increases the output as far as the MAX value.
 If the temperature or the pressure increases as far as the
opening of the thermostat/pressure switch, the burner pro-
6.7

Ignition failure

If the burner does not switch on, there is a lockout within 3s of the
electrical supply reaching the gas valve.
It may be that the gas does not arrive at the combustion head
within the safety time of 3 s.
In this case, increase gas delivery upon ignition.
The arrival of the gas at the pipe coupling is shown on the pres-
sure gauge of Fig. 37 at page 37.
6.8

Burner flame goes out during operation

If the flame accidentally goes out during operation, the control
box carries out a recycle (i.e. it repeats the start-up phase once,
and makes a further ignition attempt).
If the flame is still absent, the control box goes into lockout.
Start-up, calibration and operation of the burner
gressively reduces the output as far as the MIN value.
 The burner switches off when the request for heat is lower
than the heat supplied by the burner at MIN output.
 The thermostat/pressure switch TL opens and the control
box carries out the switching off phase.
 The damper closes completely to reduce thermal disper-
sions to a minimum.
In the event of a burner lockout, more than two
consecutive burner reset operations could cause
damage to the installation. On the third lockout,
contact the Aftersales Service.
WARNING
If further lockouts or burner faults occur, interven-
tions must only be made by qualified, authorised
personnel (as indicated in this manual, and in
compliance with the laws and regulations current-
DANGER
ly in force).