Approvals
The PAC2200CLP conforms to the regulations of the European directives.
• CE conformity
Applied directives and standards can be found in the EU Declaration of Conformity
(https://support.industry.siemens.com/cs/ww/en/ps/7KM2200-2EA00-1JB1/cert).
• MID conformity (optional)
DE MTP 17 B 008 MI-003
Only devices with the following MLFB numbers have MID approval:
7KM2200-2EA00-1JB1
7KM2200-2EA40-1JB1
As per the Measuring Instruments Directive (MID), Annex 1, Point 10, the following
displays and the functions that cause them are within the MID application range and
therefore formed part of the conformity assessment procedures according to MID, Annex
II, Module B.
Not included in the application range are in particular:
– Outputs with the exception of the test LED
PAC2200CLP
Equipment Manual, 06/2021, L1V30820585B-02
Energy for the overall measured
values formed from all the exist-
ing measurement systems, OBIS
code
Positive active, 1.8.0
T1 + T2 kWh
secondary side
(menu item kWh IMPORT 11.10)
Positive active, 1.8.0
T1 + T2 kWh
primary side
(menu item kWh IMPORT 11.8)
Negative active, 2.8.0
T1 + T2 kWh
primary side
(menu item kWh EXPORT 11.9)
Negative active, 2.8.0
T1 + T2 kWh
secondary side
(menu item kWh EXPORT 11.11)
Short code
Phase angle range of the
offset between current
Energy
and voltage
+A
> 270° to < 90°
+A
> 270° to < 90°
-A
> 90° to < 270°
-A
> 90° to < 270°
Technical specifications
8.1 Technical specifications
Revision
0
1
1
1