)* Formula:
Example:
Pulses per unit: 50
Pulse divider: 100
Unit: kWh
"Digital output" parameter
The following functions can be assigned to the "Digital output" parameter:
• Energy pulse output; can be programmed for active or reactive energy pulses
• Indication of the direction of rotation
• Operating state display of the device
• Switching output for remote control via the Modbus interface
Selection
ACTION
PULSES PER UNIT
PRO
(Output pulse divider)
PAC2200CLP
Equipment Manual, 06/2021, L1V30820585B-02
Range
OFF:
Output is deactivated.
DEVICE ON:
Output signals that the device is switched on.
REMOTE CONTROL:
Output is controlled by remote access.
DIRECTION OF ROTATION:
Output is switched on by an electric counter-
clockwise rotating field and remains active for as
long as the field is rotating in this direction.
PULSE:
Digital output signals the number of pulses set for
each energy unit (e.g. kWh). The energy counter
specified in the "COUNTER SOURCE" field is evaluat-
ed here.
The "PULSES PER UNIT" property is only visible if "PULSE
INPUT" is set for the "ACTION".
Range: 1 to 4000
The "PULSES PER UNIT" property is only visible if "PULSE
INPUT" is set for the "ACTION".
Range: 1; 10; 100; 1000
Commissioning
6.3 Parameterizing the device
Factory setting
OFF
1
1
67