Connection elements
The specified conductor cross-sections describe the capacity of the connection terminals.
When selecting the conduction cross-sections, always pay attention to the possible current
load and ensure adequate cable protection.
Current, power supply
Conductor cross-section for copper cable (Cu)
2-wire, same cross-section
Tightening torque
Conductor cross-section for copper cable (Cu) for
UL market
Conductor cross-section for copper cable (Cu) for
CSA market
PAC2200CLP
Equipment Manual, 06/2021, L1V30820585B-02
Rigid
Flexible
Flexible with end sleeve, without plastic
sleeve
Flexible with end sleeve and plastic sleeve
Rigid
Flexible
Flexible with end sleeve, without plastic
sleeve
Flexible with TWIN end sleeve and plastic
sleeve
Technical specifications
8.1 Technical specifications
5 A device
0.2 ... 6.0 mm
2
[AWG 24...10]
0.2 ... 4.0 mm²
[AWG 24...12]
0.2 ... 4.0 mm²
[AWG 24...12]
0.25 ... 4.0 mm²
[AWG 24...12]
0.2 ... 1.5 mm²
[AWG 24 ... 16]
0.2 ... 1.5 mm²
[AWG 24 ... 16]
0.25 ... 0.75 mm²
[AWG 24 ... 19]
0.5 ... 2.5 mm²
[AWG 20 ... 14]
0.5 ... 0.6 Nm
[4.4 ... 5.3 lb-in]
AWG 10 ... 4
Solid or stranded with ferrules
AWG 8 ... 4
Compact stranded
65 A device
0.75 ... 35 mm²
[AWG 19 ... 2]
1 ... 35mm²
[AWG 18 ... 2]
0.75 ... 25 mm²
[AWG 19 ... 4]
0.75 ... 25 mm²
[AWG 19 ... 4]
0.75 ... 10 mm²
[AWG 19 ... 8]
1 ... 4mm²
[AWG 18 ... 12]
0.75 ... 4 mm²
[AWG 19 ... 12]
0.75 ... 4 mm²
[AWG 19 ... 12]
3 Nm
[26.6 lb-in]
81