Connection Examples - Siemens SENTRON PAC2200CLP Product Manual

7km power monitoring device
Hide thumbs Also See for SENTRON PAC2200CLP:
Table of Contents

Advertisement

4.3

Connection examples

Some connection examples for the following types of connection are listed below:
• 1P2W - 1 phase, 2 conductors
• 3P4W - 3 phases, 4 conductors
The selection of the connection types in the device can differ according to the device version.
For the 5 A device, it is only possible to measure the current with current transformers.
For the 65 A device, no current transformers may be connected.
All input or output terminals not required for measuring remain free.
Parameterization of the devices is described in chapter Parameterizing the device (Page 60).
NOTICE
Grounding of current transformers optional
The connection of the transformers and thus also the grounding of the transformers on the
secondary side must always be carried out according to the applicable regulations.
Grounding of the current transformers on the secondary side is not necessary for use in low-
voltage switchboards for performing measuring tasks.
PAC2200CLP
Equipment Manual, 06/2021, L1V30820585B-02
Connection
4.3 Connection examples
43