Technical specifications
8.1 Technical specifications
Measuring inputs
Measuring category
Input resistance (L-N)
Measuring inputs for current (5 A device)
Only for connection to AC power systems via external current transformers (5 A device)
Measuring inputs
Rated current In I
Max. permissible continuous current
Current impulse overload capability
Zero point suppression level
Measuring range
Apparent power consumption
Measuring inputs for current (65 A device)
For direct connection to the AC system.
Measuring inputs
Reference current Iref (acc. to EN 50470-1)
Max. input current Imax
Current impulse overload capability
Measuring range
Power supply (5 A and 65 A devices)
Power supply
Design of the power supply
Operating range
Power consumption
Overvoltage category
78
e
Measuring range 1 A / per phase
Measuring range 5 A / per phase
CAT III (acc. to IEC 61010-2-030)
1 MΩ
1 A / 5 A
10 A
100 A for 1 s
10 mA / 45 mA
1 ... 120%
4 mVA
0.115 VA
10 A
65 A
1990 A for 10 ms
0.5 ... 65 A
Wide range AC power supply
(supply from measuring voltage L1, L2 or L3)
100 V - 230 V +/- 20%
5 VA
OVC III
Equipment Manual, 06/2021, L1V30820585B-02
PAC2200CLP