A S S E M B L Y O F T H E S W I T C H G E A R O N S I T E

Busbars for 12 kV units

Busbars are made of copper and have a flat
cross-section for rated current up to 2500 A.
For 3150, 3600 and 4000 A, the busbars have a
double D-shaped cross-section. Branch conductors
always have a flat cross-section.
12 kV bushings are made of epoxy resin
castings and are arranged as a single casting for
all three phases. For bus-tie units the bushings
are single and are arranged in the lower part of the
unit. Bushings are held in bushing plates.
40
nr. 4
10x35 screws
42
nr. 8
M10 washers
43
nr. 4
M10 nuts
Figure 41 12 kV panels – T-off 630-1250 A, busbars 1250 A
41
nr. 4
10x60 screws
42
nr. 8
M10 washers
43
nr. 4
M10 nuts
Figure 42 12 kV panels – T-off 630-1250 A, busbars 1600 A-2000 A-2500 A
For 12 kV, the busbars are bare (without insulation)
and without insulating covers up to 1250 A.
1600, 2000, 2500, 3150, 3600 and 4000 A open
D-shaped busbars are fitted with insulating
covers.
33
40
42
43
41
42
42