CALIBRATION SETTINGS:
1. Select CALIBRATION using the function selection buttons
2. Press and hold the right-arrow key for 2 seconds on the primary
TC5-ITA unit to start the calibration.
3. Once the calibration is launched, press and hold the right-arrow
key for 2 seconds on all TC5-ITA slave units within the next 30 sec-
onds.
4. After 30 seconds, the environment controller enters in test mode
and starts simulating the room temperature. The simulated room
temperature gradually increases for TC5-ITA units to detect the
number of On/Off and variable ventilation stages in use.
5. After the environment controller has reached the start tempera-
ture of its last ventilation stage, press and hold the right-arrow key
of the PRIMARY TC5-ITA unit for 2 seconds to end the calibration.
You can also wait for the environment controller to reach 120°F
(49°C) – the calibration will automatically end at that moment.
One reference point per ventilation stage will then be added to
each calibrated TC5-ITA.
6. Refer to the programming chapter to assign an inlet opening to
each reference point.