Adjust the Reset Delay:
This is the delay that is required to fully open / close the inlet panel in order
to reset the inlet position. The reset delay of an inlet must be greater than
its total opening time. This ensures the inlet panel to be completely opened
or closed while its position is being reset.
The Reset Delay can be adjusted from 60 to 900 seconds in increments of
15 seconds.
Select "RESET SETTINGS" using the function selection buttons.
Press the right-arrow key until the Reset Delay is displayed alter-
nating with letters "dEL".
Use the adjustment buttons to set the Reset Delay to the desired
value.
Proceed in similar fashion to set the Reset Delay on all
TC5-ITA units.
Manual & Automatic Resets
The reset of an inlet can either be performed manually (which is useful
when the user detects an offset in the inlet position) and/or it can be per-
formed at regular intervals (auto-reset).
Manual Reset:
To perform a manual reset, switch internal switch #9
from OFF to ON.
Automatic Reset:
Set internal switch #7 to ON to enable the auto-
reset function then program the auto-reset settings
as explained in the following section.
TC5-ITA
ON
OFF
ON
OFF
TC5-ITA rev.02


25