Installing the PRO4200 Two Reader Module

Power

Table 3: Additional PRO4200 Two Reader Module LEDs
LED number
D6
D7
D8
D9
D10
D11
D12
D13
D14
D15
D16
D17
D18
D19
D20
Power
The Two-Reader Module accepts 12VDC with an operating range of 10 to 14VDC
and consumes a maximum of 300mA of current without readers. Locate power source
as close to this board as possible. Connect power with minimum of 18 AWG wire.The
input voltage is regulated to 5VDC.The regulated voltage or the 12VDC (pass
through) is available for powering the readers. The selection is made via jumpers and
is available at both reader connectors.
Note: POLARITY for 12VDC power is important. Make sure the +12 VDC is connected to
the terminal labeled +12V and the return is connected to the terminal labeled GND.

Communications

The Two-Reader Module communicates to the host controller via an RS-485
interface.The interface allows for multi-drop communication of up to 4,000 feet
16
Description
Input1
Input 2
Input 3
Input 4
Input 5
Input 6
Input 7
Tampert
Power
Relay 0 status
Relay 3 sttatus
Relay 2 status
Relay 4 status
Relay 1 status
Relay 5 status
www.honeywell.com