Installing the PRO4200 Two Reader Module
Wiring Diagram for Connectors TB1,TB7-9
OP40HONE, OP90HONE, OT30HONA, OT31HONA, OT35HONA, and
OT36HONA.
Each reader port supports a reader with TTL interface. Power to the reader is
selectable as 5VDC or 12VDC (pass-through). This selection is done by setting the
jumpers J2 for reader 1 and J3 for reader 1. Set jumper at position "5" for 5VDC or
"12" for pass-through 12VDC. The factory defaults set J2 and J3 to "5".
For wiring to a reader port
Table 4: Settings for Wiring to a Reader Port
Terminal
1
2
3
4
5
6
The LED control terminal in each reader port can be configured via host software to
support one-wire single or bi-colored reader LED. An example of the most common
configuration is shown below. If Beeper Control is not used, its terminal can be
programmed to be the second wire for the two-wire bi-colored reader LED.
Table 5:
LED Output->
Single Color LED
Bi- Color LED
To fully utilize each reader port, a 6-conductor cable (18AWG) is required. Reader
port configuration is set via host software
Input Wiring
Inputs 0 to 7 may be configured to use normally open or normally closed contacts and
non-supervised or supervised (with standard ±1% tolerance 1K ohm). Four of these
20
Typical Wire
Color
Red
Power (5 or
12 Vdc)
Brown
LED control
Yellow
Beeper
Control
White
Data 1
Signal
Green
Data 0
Signal
Black
Common
High
Tri- Stated
LED ON
LED OFF
Green LED ON
Both LEDs OFF
Wiegand
Clock/Data
Reader
Readers
Power (5 or 12
Vdc)
LED control
Beeper
Control
Clock Signal
Data 0
Signal
Common
Low
LED OFF
Red LED ON