CHAPTER 3 - WATER HEATER START-UP
3.5.

DHW Frost Protection

The Indirect Water Heater (IDWH) Sensor used in the
Prestige Excellence provides a Frost Protection feature
to the water heater. The Frost Protection feature is de-
signed to protect the Excellence water heater from
a potential freeze up. Frost Protection will generate
a DHW call once the IDWH temperature falls below
42º F [6ºC]. Once Frost Protection is activated, the inter-
nal circulator and diverter valve will direct water flow
to the water heater and the burner will fire. Frost Pro-
tection will end once the IDWH temperature is raised
to 60ºF [16ºC]. This feature is always active and cannot
be disabled. Frost Protection is still active even if DHW
operation has been disabled.
3.6.

CTRLMax Factory Settings

DHW SETTING
DHW Operation
Demand Type
DHW Boiler Setpoint
DHW Setpoint
DHW On Differential
DHW Storage Adder
DHW Post pump time
DHW Priority Timeout
DHW Priority
DHW Call Blocking
DHW to CH Call Blocking
Antilegionella Function
12
FACTORY
MINIMUM
DEFAULT
SETTING
Enabled
Sensor
168°F [75°C]
96°F [35°C]
140°F [60°C]
68°F [20°C]
6°F [3°C]
4°F [2°C]
28°F [15°C]
10°F [5°C]
2 Minutes
Off
Off
Off
Enabled
1 Minute
0 Minute
0 Minute
0 Minute
Enabled
MAXIMUM
EZ SETUP RESET
SETTING
188°F [87°C]
3
168°F [75°C]
3
18°F [10°C]
54°F [30°C]
30 minutes
120 Minutes
3
30 Minutes
30 Minutes
Enabled
INSTALLER RESET
3
3
3
3
3
3
3
3
3
3
Disabled