Commonwealth Of Massachusetts Installation; T&P Relief Valve Discharge Piping; Domestic Drain Valve; Standard Installation - TriangleTube PRESTIGE Excellence 110 Installation & Maintenance Manual

Indirect water heater
Hide thumbs Also See for PRESTIGE Excellence 110:
Table of Contents

Advertisement

CHAPTER 2 - DOMESTIC PIPING
T&P Relief
Valve w/ 3/4"
Tee
DHW Hot
Water Outlet
2.3.
Commonwealth of Massachusetts In-
stallation
Follow this procedure for jurisdictions requiring a vacuum
breaker to be installed on the domestic cold water inlet.
Install the T&P in the run (straight through leg) of a tee
located at the domestic hot water outlet. Use a long el-
ement T&P relief valve, as shown in Fig. 2 above.
2.4.
T&P Relief Valve Discharge Piping
T&P relief valve discharge piping must be:
Made of material serviceable for temperatures
of 250ºF or greater.
Directed so that hot water flows away from all
persons.
Directed to a suitable place for disposal.
Installed so as to allow complete draining of the
T&P relief valve and discharge line.
T&P relief valve discharge piping must not be:
Excessively long. Using more than 2 elbows or
15 feet of piping can reduce discharge capacity.
Directly connected to a drain. Terminate dis-
charge piping within 6" from drain. Refer to lo-
cal codes.
Plugged, reduced or restricted.
Subject to freezing.
4
C
Fig. 2 - Commonwealth of Massachusetts Installation
lief valve and tank connection or on T&P re-
lief valve discharge piping. Do not plug T&P
relief valve or discharge piping. Improper
placement and piping of T&P relief valve can
cause severe personal injury, death or sub-
2.5.
Drain valve and fittings are supplied by others.

2.5.1 Standard Installation

Drain
Dip Tube
3/4" Brass Close
Nipple
DHW Aux. Connection
Air Vent Connection
DHW Cold Water
Inlet
WARNING
Do not install any valve between T&P re-
stantial property damage.

Domestic Drain Valve

Install a tee connection at the domestic cold
water inlet, as shown in Fig. 4 on page
Pipe the drain valve piping from the tee con-
nection to:
Ū a suitable place for disposal
or
Ū terminate within 12" of the floor
D
C
7.

Advertisement

Table of Contents
loading

Table of Contents