Advertisement

System overview
2.5 System data
Biological environmental conditions
Long-term storage
Transport
Operation
Climatic environmental conditions
Long-term storage
Transport
Operation
Mechanical environmental conditions
Long-term storage
Transport
Operation
Vibration test in operation
Shock test in operation
Installation altitude
Operation
Permissible cooling medium tem-
perature (air) and installation alti-
tude in operation
Product packaging (storage packaging) is individual packaging for storage - and does not satisfy the requirements for
1)
transport. As a consequence, product packaging is therefore not suitable for shipping.
Transport packaging is either packaging that is directly suitable for transport - or secondary packaging, which together
2)
with the product packaging, satisfies the requirements for transport.
36
Class 1B1 according to EN 60721-3-1, in product packaging
Class 2B1 according to EN 60721-3-2, in transport packaging
Class 3B1 according to EN 60721-3-3
Class 1K4 according to EN 60721-3-1, in product packaging
Temperature: -25 ... +55 °C
Class 2K4 according to EN 0721-3-2, in transport packaging
Temperature: -40 ... +70 °C
Class 3K3 according to EN 60721-3-3 with increased ruggedness with respect to
relative humidity
Temperature: 0 ... +40 °C without derating
> 40 ... +55 °C with reduction of the output current by 2.67 % pro °C
Relative humidity: 5 ... 95 % no condensation (better than Class 3K3)
Oil mist, salt mist, ice formation, condensation, dripping water, spraying water,
splashing water and water jets are not permitted
Class 1M2 according to EN 60721-3-1, in product packaging
Class 2M3 according to EN 60721-3-2, in transport packaging
Class 3M1 according to EN 60721-3-3
According to IEC 60068-2-6 test Fc (sinusoidal)
10 ... 57 Hz: 0.075 mm deflection amplitude
57 ... 150 Hz: 1g acceleration amplitude
10 frequency cycles per axis
According to IEC 60068-2-27 test Ea (half-sine)
5 g peak acceleration
30 ms duration
3 shocks in all three axes in both directions
0 ... 1000 m above sea level without derating
> 1000 ... 4000 m
Reduction of the output current by 10 % per 1000 meters, or
Reduction in the ambient temperature by 5°C per 1000 meters
> 2000 ... 4000 m
Operation on line supply systems with grounded neutral point, or
Operation on an isolation transformer with secondary grounded neutral
0 °C ... +40 °C and an installation altitude of up to 1000 m without derating,
>40° C to +55 °C: Reduction of the output current by 2.67 % pro °C
Installation altitude > 1000 ... 4000 m: Reduction in the ambient temperature by 3.5°C
per 500 m.
1)
2)
1)
2)
1)
2)
Power Units in Booksize C/D-Type Format
Manual, 01/2017, 6SL3097-4AC20-0BP1