Nivotemp NT MD 1 Introduction 1.1 Intended Use Level switches are used to monitor the liquid level and temperature in fluid systems. Level switches must not be used in highly flammable or corrosive liquids. The medium must not contain particles, particularly metallic particles, to prevent deposits on the float or between the float and switching tube.
Nivotemp NT MD 1.4 Model key XX XX XX XX XX NT MD XX XX Options = Oval flange Model designation = Adapter G3/4 to G1 Version LED temperature display 2 x temperature output Connection G3/4 4 x temperature output...
Nivotemp NT MD 2 Safety instructions 2.1 Important advice Operation of the device is only valid if: – the product is used under the conditions described in the installation- and operation instruction, the intended application according to the type plate and the intended use. In case of unauthorized modifications done by the user Bühler Technolo- gies GmbH can not be held responsible for any damage, –...
Nivotemp NT MD 2.2 General hazard warnings The equipment must be installed by a professional familiar with the safety requirements and risks. Be sure to observe the safety regulations and generally applicable rules of technology relevant for the installation site. Prevent malfunctions and avoid personal injuries and property damage.
Nivotemp NT MD 3 Transport and storage Only transport the product inside the original packaging or a suitable alternative. The equipment must be protected from moisture and heat when not in use. It must be stored in a covered, dry, dust-free room at room temperature.
Nivotemp NT MD 4 Setup and connection DANGER Electric voltage Risk of electric shock a) Always disconnect the unit from the mains before performing work. b) Secure the equipment from accidental restarting. c) The equipment may only be installed, maintained and put into operation by instruc- ted, competent personnel.
Nivotemp NT MD 4.2 Electrical connections Electricity is supplied via plug connectors. Please refer to the appendix for installation dimensions, nominal voltage and plug configuration. The temperature switching outputs are PNP transistors (see illustration): Supply voltage Note: When measuring the switching output with high-load measuring device inputs or when used as a frequency output, the load must be set to 10 kΩ...
Page 12
Nivotemp NT MD Voltages and currents All Bühler level contacts with reed switch can switch minimal Switching voltages of 10 µV and minimal switching currents of 1 µA. The maximum values specified for the respective contact types apply. Level contact with reed switches can therefore be used for SPS applications as well as for high loads (within the maximum lim- its) without hesitation.
Nivotemp NT MD 5 Operation and control NOTICE The device must not be operated beyond its specifications. 5.1 Start-up procedure The device will automatically switch on when connected to power. It will first briefly display the software version, at which time the device will also check the built-in components.
Nivotemp NT MD 5.3 General key functions The keys below the display are used for operation. The menu controls are detailed in the following chapters. Mode Function – Measurement display: Change measured variables displayed. – In the menu: Move down one menu level.
Nivotemp NT MD 5.5 Menu overview The menu structure is based on the VDMA standard sheet 24574-1. The menu structure is hierarchic. The top menu level contains the main menu items, e.g. tEMP, F, diA, E. Each main menu has additional submenu items.
Nivotemp NT MD 5.6 Changing basic settings The general basic settings can be changed under menu Basic Settings Extended Functions (bEF). These settings will affect the measurement display and the configuration options in the various main menus. Here you can also change the switching output assignment.
Nivotemp NT MD 5.6.3 Set temperature unit This is where the unit symbol for the temperature is configured: t. u ni Selection menu Basic EF b. E F Set Unit Temp Basic Adv. Functions Temperature unit ; C - ; F...
Nivotemp NT MD 5.6.6 Restore factory settings (Reset) Use the Reset function (rES) to restore the factory settings. All changes will be lost. Since this will also reset the limits, you must check the temperature settings. b. E F Reset...
Nivotemp NT MD Version with 4 switching outputs: Switching outputs Version with analogue output: Analogue output A1. H i A1. L o A. o u1 Diagnostic settings: Diagnostics SJ. o u out1 dt. M M 0. 0 5.7 Switching outputs All switching outputs are configured the same way.
Nivotemp NT MD 5.7.1 Switching output x: Definition of the switching characteristic The switching characteristic for the output can be configured under the following menu: ____ Measured variable Out X out_ EF X Set Out X Selection menu Settings menu OUTX...
Nivotemp NT MD Note: The designation of the switching function may vary: Measured variable closed open closed open rising NO contact rising NC contact falling NC contact falling NO contact NO (normally open) NC (normally closed) 5.7.2 Switching output x: Upper switching limit (switching point)
Nivotemp NT MD 5.7.4 Switching output x: Switch-on delay The menu Advanced Functions is used to configure additional settings for switching output x. The submenu is at the second submenu level. The switching and switch-back delay prevents the alarm being triggered too frequently in unstable conditions. The switching...
Nivotemp NT MD 5.7.7 Change status LED display function The LEDs in the display indicate the switching status of the output. The following table shows how LEDs are allocated to the switching output: Numbering Switching Assignment for Assignment for Assignment for...
Nivotemp NT MD The options are: LED = output; LED = -output; the LED lights up when the PNP switching output the LED lights up when the PNP switching output is closed. is open. NOTICE The display function of the status LED affects event logging! Please note chapter “Dia- gnostic options”.
Nivotemp NT MD 5.8.4 Analogue output x: Testing the analogue output The analogue output can be tested. The highest, mean and lowest analogue value can be output successively. This is configured in menu: ____ Analog OutX Check AnX C. A n_...
Nivotemp NT MD The information displayed will alternate between the index and time for entry x, e.g. Jor1 ⇔ 1. 4 h for the most recent event 1.4 hours ago. Press the key to return to the submenu or use to select the next journal entry.
Nivotemp NT MD 5.9.4 Delay for storing the Min/Max Temperature A delay time for saving the minimum and maximum temperature can be set to record reliable values when temperatures fluc- tuate. Here, enter the time span in seconds during which the signal must be continuously present before the temperature is logged.
Nivotemp NT MD 6 Cleaning and Maintenance This device is maintenance-free. The method for cleaning the devices must be adapted to the IP protection class of the devices. Do not use cleaners which could damage the device materials. Bühler Technologies GmbH...
Nivotemp NT MD 7 Service and repair This chapter contains information on troubleshooting and correction should an error occur during operation. Repairs to the unit must be performed by Bühler authorised personnel. Please contact our Service Department with any questions: Tel.: +49-(0)2102-498955 or your agent...
Nivotemp NT MD Possible errors Problem / Malfunction Possible cause Action Switching output not trigger- – Switching output configured incorrectly – In submenu Coux: “Test Switching Output“ to ing when exceeding limits ensure normal mode – Switching output defect – In submenu Coux: “Test Switching Output” to...
Nivotemp NT MD 8 Disposal Dispose of parts so as not to endanger the health or environment. Follow the laws in the country of use for disposing of elec- tronic components and devices during disposal. BE100022 ◦ 11/2020 Bühler Technologies GmbH...
Nivotemp NT MD 9 Appendices 9.1 Technical Data NT MD Version Dimensions Operating pressure: max. 1 bar M12x1 Operating temperature: -20 °C to +80 °C Float: SK 161 Min. fluid density: 0.80 kg/dm³ Lengths: 280, 370, 500 mm (standard) LEDs variable to max.
Nivotemp NT MD 9.2 Temperature outputs NT MD Choose from the following temperature outputs: 1T-KT Plug (base) 2 x M12 – 4-pin 2 x M12 – 4-pin 1 x M12 – 4-pin 1 x M12 – 8-pin Switching outputs 2 x freely programmable*...
Nivotemp NT MD 9.4 Current settings Switching outputs Basic Settings Diagnostics o. u ni SJ. o u t. u ni dt. M M o. H i o. L o r. o u1 r. o u2 r. o u3 r. o u4...
Page 35
Nivotemp NT MD none (non2) (2 fixed-point numbers) Range x Resolution x < 5 0.01 5 <= x < 10 0.02 10 <= x < 20 0.05 20 <= x < 50 50 <= x < 100 100 <= x Example no unit: Min = 100, Max = 1500 ->...
Nivotemp NT MD 9.7 Menu Sequence Overview Main menu Submenu 1 Submenu 2 Submenu 3 Settings and Display Menu Configuration t___ Shortcut Equipment configuration or 60s no action: Exit main/submenu ____ ____ Display Switch ____ ____ Switches the measurement display level/temperature...
Page 39
RMA-Formular und Erklärung über Dekontaminierung RMA-Form and explanation for decontamination RMA-Nr./ RMA-No. Die RMA-Nummer bekommen Sie von Ihrem Ansprechpartner im Vertrieb oder Service./ You may obtain the RMA number from your sales or service representative. Zu diesem Rücksendeschein gehört eine Dekontaminierungserklärung. Die gesetzlichen Vorschriften schreiben vor, dass Sie uns diese Dekontaminierungserklärung ausgefüllt und unterschrieben zurücksenden müssen.