Huawei FusionModule1000A40 Initial Configuration Parameter Manual page 65

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule1000A40:
Table of Contents

Advertisement

Initial Configuration Parameters of the Electric Heater Temperature Controller for Air Conditioner Pipes
Category
SET
Specified value
Hy
Temperature difference
AC
Anti-frequent–startup delay
Adjustment parameters
Cy
Probe error, compressor running time
Cn
Probe error, compressor stop time
CH
Control direction (cooling cL, heating Ht)
id
Defrosting time interval
Defrosting parameters
Md
Maximum allowed defrosting time
Display the temperature during the defrosting period (rt = actual warehouse temperature; it =
dF
temperature before defrosting starts; St = specified value; dF = abbreviation of defrosting
Initial Configuration Parameters of the Electric Heater Temperature Controller for Fireproof Doors
Category
Specified value
SET
Hy
Temperature difference
AC
Anti-frequent–startup delay
Adjustment parameters
Probe error, compressor running time
Cy
Cn
Probe error, compressor stop time
Control direction (cooling cL, heating Ht)
CH
id
Defrosting time interval
Defrosting parameters
Maximum allowed defrosting time
Md
Display the temperature during the defrosting period (rt = actual warehouse temperature; it =
dF
temperature before defrosting starts; St = specified value; dF = abbreviation of defrosting
Item
Item
Default Value
Value Range
N/A
–55°C to 99°C
2.0°C
0.1°C to 25°C
1
0–50 min
15
0–99 min
30
0–99 min
cL
cL–Ht
6
0–99 h
30
0–99 min
it
rt – it – St – dF
Default Value
Value Range
–55°C to 99°C
N/A
2.0°C
0.1°C to 25°C
1
0–50 min
15
0–99 min
30
0–99 min
cL
cL–Ht
6
0–99 h
30
0–99 min
it
rt – it – St – dF
Factory Setting
Remarks
40°C
N/A
5.0°C
N/A
1
N/A
0
N/A
0
N/A
Ht
N/A
0
N/A
0
N/A
it
N/A
Factory Setting
Remarks
15°C
N/A
5.0°C
N/A
1
N/A
0
N/A
0
N/A
Ht
N/A
0
N/A
0
N/A
it
N/A