Huawei FusionModule1000A40 Initial Configuration Parameter Manual page 40

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule1000A40:
Table of Contents

Advertisement

Component
UPS-1/2 QF
MCCB Current Parameter Settings
Category
Parameter
Default Value
Value Range
Setting
Remarks
0000–1111
L overload protection (DIP switch setting)
1111
0(0.04)1(0.08)1(0.16)0(0.32)
Step 0.04, can be set from 0.4 to 1
0000–1111
I protection (transient short circuit protection)
Electronic MCCB current setting
Step 0.5, can be set from 1 to 10
/
/
I = 1 - 1.5 - 2 - 2.5- 3 - 3.5 - 4.5-
S protection (delayed short circuit protection)
5.5 - 6.5 - 7 - 7.5 - 8 - 8.5 - 9 - 10×In

Advertisement

Table of Contents
loading

This manual is also suitable for:

V200r003c10

Table of Contents