Huawei FusionModule1000A40 Initial Configuration Parameter Manual page 25

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule1000A40:
Table of Contents

Advertisement

Monitoring
Data
Device
Device
Device
Type
Name
Name
Collector_ECC8
FE
52274255
CRAC-A1
00
Collector_ECC8
FE
52274255
CRAC-B1
00
Collector_ECC8
FE
52274255
CRAC-C1
00
Collector_ECC8
FE
52274255
CRAC-D1
00
Collector_ECC8
FE
02290838
UPS-1
00
Collector_ECC8
FE
02312QAD
UIM20A-1
00
Collector_ECC8
Dry
52250103
FAULT RELAY
00
contact
Collector_ECC8
Dry
52250103
LOCAL FIRE
00
contact
Collector_ECC8
Dry
52250103
FIRE RELAY
00
contact
Collector_ECC8
Dry
Door Status
33010007
00
contact
Sensor-1
Collector_ECC8
Dry
Door Status
33010007
00
contact
Sensor-2
Collector_ECC8
Dry
Water Sensor-
33010347
00
contact
1
Collector_ECC8
Dry
/
AC PDB-1 SPD
00
contact
Collector_ECC8
Dry
Power PDB-1
/
00
contact
SPD1
Collector_ECC8
Dry
Power PDB-1
/
00
contact
SPD2
Device IP
Device
Device Model
Address
Address
NetCol5000-A025H4WE2
/
NetCol5000-A025H4WE2
/
NetCol5000-A025H4WE2
/
NetCol5000-A025H4WE2
/
UPS5000-E-125K-HASBS
/
UIM20A
/
SIGMA XT/K11031M2
/
SIGMA XT/K11031M2
/
SIGMA XT/K11031M2
/
POLYMR M520/
/
GREYSTONE GS-06
POLYMR M520/
/
GREYSTONE GS-06
GREYSTONE WD-
/
900D/POLYMRY W517K
/
/
/
/
/
/
WebUI User
Alarm
LCD User Name
Name and
Threshold
and Password
Password
User name:Admin
/
/
/
Initial password:
User name:Admin
/
/
/
Initial password:
User name:Admin
/
/
/
Initial password:
User name:Admin
/
/
/
Initial password:
User name:admin
User name:admin
/
/
Initial password:
Initial password:
Changeme
/
/
/
Normal: open
/
/
Alarm: closed
Normal: open
/
/
Alarm: closed
Normal: open
/
/
Alarm: closed
Normal: closed
/
/
Alarm: open
Normal: closed
/
/
Alarm: open
Normal: closed
/
/
Alarm: open
Normal: closed
/
/
Alarm: open
Normal: closed
/
/
Alarm: open
Normal: closed
/
/
Alarm: open
Port to
DDF
Upper-
Upper-
Transfer
Level
Level
Port
Device
Device
Smart ETH
FE
/
Gateway-2
000001
Smart ETH
FE
/
Gateway-2
000001
Smart ETH
FE
/
Gateway-2
000001
Smart ETH
FE
/
Gateway-2
000001
Smart ETH
FE
/
Gateway-3
000001
Smart ETH
/
FE
/
Gateway-3
Crimped
Collector_ECC
/
/
terminal
800
Crimped
Collector_ECC
/
/
terminal
800
Crimped
Collector_ECC
/
/
terminal
800
Crimped
Collector_ECC
/
/
terminal
800
Crimped
Collector_ECC
/
/
terminal
800
Crimped
/
/
UIM20A-1
terminal
Crimped
/
/
UIM20A-1
terminal
Crimped
/
/
UIM20A-1
terminal
Crimped
/
/
UIM20A-1
terminal
Upper-Level
Remarks
Device Port
Settings > Comm Settings > IP Settings
POE_1
Set IP assigning mode to Automatic
(DHCP).
Settings > Comm Settings > IP Settings
POE_2
Set IP assigning mode to Automatic
(DHCP).
Settings > Comm Settings > IP Settings
POE_3
Set IP assigning mode to Automatic
(DHCP).
Settings > Comm Settings > IP Settings
POE_4
Set IP assigning mode to Automatic
(DHCP).
Settings > Comm Settings > IP Settings
POE_1
Set IP assigning mode to Automatic
(DHCP).
POE_3
/
AIDI_1
Extinguishant Control Panel
AIDI_2
Extinguishant Control Panel
AIDI_3
Extinguishant Control Panel
COM1/AIDI_4
/
COM2/AIDI_5
/
COM1/AI/DI_1
/
COM3/AI/DI_3
/
COM5/AI/DI_5
/
COM7/AI/DI_7
/

Advertisement

Table of Contents
loading

This manual is also suitable for:

V200r003c10

Table of Contents