Huawei FusionModule1000A40 Initial Configuration Parameter Manual page 13

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule1000A40:
Table of Contents

Advertisement

Component
Main PDF-1
Parameter
Category
Password
Number of Phases LN1
System
Configuration
Configuration
Number of Phases LN2
attributes
Volt Threshold Min LN1
Volt Threshold Min LN2
Voltage
Thresholds
Volt Threshold Max LN1
Volt Threshold Max LN2
Volt Hysteresis Min LN1
Voltage
Hysteresis
Volt Hysteresis Min LN2
Device
Configuration
Volt Hysteresis Max LN1
Voltage
Hysteresis
Volt Hysteresis Max LN2
Freq Threshold Min LN1
Freq Threshold Min LN2
Frequency
Thresholds
Freq Threshold Max LN1
Freq Threshold Max LN2
Initial Configuration Parameters for 8D ATS
Default Value
0001
Rated Voltage
400/230 V
Rated Frequency
50 Hz
3 phases with N
3 phases with N
Secondary Load
Not Used
Generator Usage
No Generator
Line priority
Line 1–Switch I
-20%
-20%
+20%
+20%
-8%
-8%
+8%
+8%
-1%
-1%
+1%
+1%
Value Range
100/57 V-115/66 V-120/70 V-208/120 V-220/127 V-230/132 V-240/138 V-277/160 V-
347/200 V-380/220 V-400/230 V-415/240 V-440/254 V-480/277 V
50 Hz, 60 Hz
3 phases with N/3 phases without N/1 phase
3 phases with N/3 phases without N/1 phase
Not Used/Opening Only/Opening And Closing
No Generator, Generator In Use
Line 1 – Switch I/Line 2 – Switch II/No Line Priority
-30% to -5%
-30% to -5%
+5% to +30%
+5% to +30%
-29% to -4%, step 1%
-29% to -4%, step 1%
+4% to +29%, step 1%
+4% to +29%, step 1%
-10% to -1%
-10% to -1%
+1% to +10%
+1% to +10%
/
Setting
Remarks
Default Value
380/220 V
50 Hz
3 phases with N
3 phases with N
Default Value
Generator In Use
Line 1 – Switch
-10%
-10%
+10%
+10%
-8%
-8%
+8%
+8%
-5%
-5%
+5%
+5%