460 Vac Oex Switch Wiring Diagrams; Figure 27 Example Oex Switch 460Vac Wiring Diagram - KEB COMBISTOP 38 Instruction Manual

Theater load brake size 10
Hide thumbs Also See for COMBISTOP 38:
Table of Contents

Advertisement

Rectifiers
7.2.3

460 VAC OEX Switch Wiring Diagrams

Full Wave > Half Wave Rectification.
480 VAC Full Wave (432VDC) for 0.3s then 480VAC Half Wave (216VDC) holding
voltage.
Specifcation
Rated Input Voltage
Full Wave UL Current
Half Wave UL Current
Max Operating Temperature
Terminal Wire Size
NOTICE
42

Figure 27 Example OEX Switch 460VAC Wiring Diagram

Required Rectifier Specifications
 Contactors must have a minimum AC-1 rating of 24A or a minimum
AC-3 rating of 9A. An optional MOV may be used for DC coil and
contactor protection for coil voltages ≥ 180VDC.
i
 These diagrams are wiring suggestions. Other wiring solutions are
possible. Please contact KEB America, Inc. for any questions.
Value
250-500 VAC 50/60 Hz ± 10%
1.2A
0.6A
80°C
1.5mm / AWG 15
2020 KEB America, Inc.
©