No.F002 Fire Extinguishing System Conceptual Diagram (CE) - 2
-
+
+
E
ROV
SIL
AL
AUX
REMOTE
24V
CONTROL
Technical requirements:
1.All fire extinguishing signal cables are red (BOM number: 25030029) and black (BOM number: 25030073) cables with naked crimping single-wire cord end terminals (BOM number: 14170214). The red cable is positive and the black
cable is negative. The pneumatic switch, Warning signs, and fire alarm bell each has two wiring terminals that connect to two wires. The fire alarm bell is polarity insensitive. For details, see the diagram.
2.Connect a 10K terminal resistor to each of the last the fire alarm sounder and fire alarm horn/strobe in parallel.
3.Connect cables to the smoke detector and heat detector by referring to the diagram. Connect a 6.8 K terminal resistor to the last smoke and heat detectors in parallel.
4.Connect the emergency abort button and pneumatic switch to a 6.8 K terminal resistor in parallel, and to a 470 ohm resistor in serial.
5.Alarm signals are reported to the monitoring system over shielded straight-through network cables. The connection definitions are as follows: LOCAL FIRE, FIRE RELAY, and FAULT RELAY. The signal cables connect
contacts.
6.Attach cable labels to all cables connected to the extinguishant control panel, wiring terminals on electrical actuators, wiring terminals on pneumatic switches, and cables reserved for combined pre-fab. modules . See the label table for
the label content. Cable direction labels must be arranged neatly in the same direction. Cables must be bound neatly, with cable ties in the same direction. (Labels are printed on label paper with the BOM number 29041061, attached
on cable ties with the BOM number 21200708, and bound to corresponding cables.)
Smoke Detector-1
red
L1 IN
-R
red
L1 OUT
L2
black
L1 OUT
red
black red
black
+
-
+
-
+
-
+
-
+
-
+
-
+
FLT
RST
DATA
POWER
ZONE 1
ZONE 2
ZONE 3
S1
S2
STATUS UNITS
Data cable
Power cable
Connect the
Connect smoke
Connect heat
first stage
detector in
detector in
alarm to the
detection zone 1
detection zone 2
fire alarm
bell.
Terminal Resistor ( 6.8K )
Heat
Detector-1
red
L1 IN
Terminal Resistor ( 6.8K )
-R
red
L2
black
-
+
-
+
-
+
-
+
NC
C
NO
NC
C
NO
2ND
1ST
2ND
MODE
MAN
HOLD
RELEASE
SOUNDER
STAGE
STAGE
SELECT
Connect the second
Connect the
stage alarm to the
emergency
horn strobes and
abort port to
warning signs .
the
Extinguishant
abort button .
To Monitoring
system
green
brown
green
brown
& white
& white
-
+
-
+
-
+
-
NO
C
NC
C
NO
NC
C
NO
REL
LOW
FAULT
LOCAL
EXTING
EXTRACT
PRESS
PRESS
RELAY
FIRE
SWITCH
SWITCH
Connect the
Connect the
Connect the fault signal
Connect the gas release
pressure
electrical
output (NO) to the
signal output (NO) to the
actuator drive
collector of the
collector of the
signal to the
signal to the
monitoring system.
monitoring system.
pneumatic
electrical
switch.
actuator.
green
brown
& white
NC
C
NO
FIRE
RELAY
Connect the fire alarm
signal output (NO) to the
collector of the
monitoring system.