Status Register - WIKA GD-20 Operating Instructions Manual

Gas density sensor
Hide thumbs Also See for GD-20:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 37
5. Commissioning, operation
Parity
Parity
None
Even
EN
Tag number
Here, a transmitter name with up to 16 characters can be entered.
5.4.2.7

Status register

Register
Function
00200
Error memory
Error memory reset
00201
00202
Software reset
00203
Resetting to standard
After a restart (voltage supply was interrupted), the error memory is reset. Writing 0x0001 in register address 00201 has the
same effect.
Description of the error memory
Bit
Description
1
Pressure signal above the upper limit value (in bar abs., →see data sheet SP 60.77)
3
Temperature signal below the lower limit value (< -40 °C [-40 °F])
4
Temperature signal above the upper limit value (> 80 °C [176 °F])
5
Communication error pressure/ temperature sensor
Liquefaction of the SF
6
7
Gas density above the upper limit value (based on the full scale of the density measuring range in bar abs. at 20 °C [68 °F])
Recurring Modbus
10
Example: 0x0082
Bit 1 and 7 are set. The upper limit values for pressure and gas density are exceeded.
60
Register value
0 (standard)
1
Value definition, triggering the function
16 bit (see the following table)
Writing 0x0001
Writing 0x0001
Writing 0x0001
gas
6
communication error
®
WIKA operating instructions gas density sensor, model GD-20
Writable
Read only
Yes
Yes
Yes

Advertisement

Table of Contents
loading

Table of Contents