7 Control

Menu 5.11.1.1 – Heat pump
EB101
These settings are made on the display in the indoor
module.
Cooling permitted
Here you can set whether the cooling function is to be
activated for the heat pump.
Silent mode permitted
Set whether silent mode is to be activated for the heat
pump here.
Current limit
Set whether the current limiting function is to be activ-
ated for the heat pump here. During active function you
can limit the value of the maximum current.
Setting range: 6 – 32 A
Factory setting: 32 A
Stop temperature compressor
Here you can limit the value for set outdoor temperature
down to the value the heat pump is to work.
Setting range -20 – -2 °C
Factory setting -20 °C
blockFreq 1
Select a frequency range within which the heat pump
may work here.
blockFreq 2
Select a frequency range within which the heat pump
may work here.
F2040