Figure 8 Outline Drawing-200Mm Liebert Exm 480V Mbc, Two To Four Breakers, 50-100Kva - Emerson Liebert eXM User Manual

Mbc
Hide thumbs Also See for Liebert eXM:
Table of Contents

Advertisement

Figure 8
Outline drawing—200mm Liebert eXM 480V MBC, two to four breakers, 50-100kVA system
Cable Entry Area
5.3" x 7.3"
(135mm x 185mm)
8.2"
(208mm)
7.8"
(200mm)
(2000mm)
FRONT
Cable Entry Area
8.3" x 7.9"
(211mm x 201mm)
TOP
39.1 (993mm)
78.9"
RIGHT SIDE
Front
4.7"
(119mm)
34.3"
(872mm)
See
Detail A
Cable Entry Area
BOTTOM
(145mm x 211mm)
Leveler
DETAIL A
NOTES:
1. All dimensions are in inches (mm).
2. 24" (610) minimum clearance above unit
for air exhaust; 36" (914) front access required for service.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable
access plates. Remove, punch to suit conduit size
and replace.
5. Unit bottom is structurally adequate for forklift handling.
6. Control wiring and power wring must be run in
separate conduits.
7. Copper cables only are recommended.
8. All wiring is to be in accordance with national and local
electrical codes.
EXM42005
Pg. 1, Rev. 0
15
Installation Drawings
5.7" x 8.3"
®
Liebert
eXM
MBC