10-5-3. Remote Control A-B Selection
To separate using of remote control for each indoor unit in case of 2 air
conditioners are installed nearly.
Remote Control B Setup.
1. Push and hold
button on the Remote Control by the tip of the pencil.
CHECK
"00" will be shown on the display (Picture 1).
2. Press
during pushing
CHECK
disappear and the air conditioner will turn OFF. The Remote Control B
is memorized
(Picture 2).
Note : 1. Repeat previous step to reset Remote Control to be A.
2. Remote Control A has not "A" display.
3. Default setting of Remote Control from factory is A.
Unit B setup.
Press and hold MODE button for more than 20 seconds.
When A setup changed to B setup : 5 beeps will sound and operation
lamp blinks for 5 seconds.
When B setup changed to A setup : 5 beep will sound.
10-5-4. Test Operation
To switch the TEST RUN (COOL) mode, press OPERATION button for 10
seconds (The beeper will make a short beep).
. "B" will show on the display and "00" will
10-5-5. Auto Restart Setting
This product is designed so that, after a power failure, it can
restart automatically in the same operating mode as before
the power failure.
Information
The product are shipped with Auto Restart function in
the OFF position. Turn it ON as required.
How to turn ON the Auto Restart Function
• Press and hold the [OPERATION] button on the indoor
unit for 3 seconds (3 beep sounds and OPERATION lamp
blink 5 time/sec for 5 seconds).
How to turn OFF the Auto Restart Function
• Press and hold the [OPERATION] button on the indoor
unit for 3 seconds (3 beep sounds but OPERATION lamp
does not blink).
NOTE :
• In case of NO timer or OFF timer are set, AUTO
RESTART OPERATION does not activate.