7-2. Operation Data
<Cooling>
Tempeature
Model name
condition(°C)
RAS-
Indoor
Outdoor
B10J2FVG-E
27/19
35/-
B13J2FVG-E
B18J2FVG-E
<Heating>
Tempeature
Model name
condition(°C)
RAS-
Indoor
Outdoor
B10J2FVG-E
20/-
7/6
B13J2FVG-E
B18J2FVG-E
NOTES : Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor thermometer)
Heat exchanger pipe
Standard
temp.
pressure
P (MPa)
T1 (°C)
T2 (°C)
0.9-1.1
10 to 11
40 to 43
10 to 12
1.1-1.2
43 to 45
1.0-1.2
10 to 12
43 to 45
Heat exchanger pipe
Standard
temp.
pressure
P (MPa)
T1 (°C)
T2 (°C)
2.3-2.4
38 to 41
1 to 2
2.4-2.5
40 to 42
0 to 1
2.6-2.8
43 to 45
0 to 1
- 25 -
Indoor fan
Outdoor fan
Compressor
mode
mode
High
High
High
High
High
High
Indoor fan
Outdoor fan
Compressor
mode
mode
High
High
High
High
High
High
Connecting
revolution
piping
(rps)
(m)
53
5
66
77
7.5
Connecting
revolution
piping
(rps)
(m)
76
5
86
83
7.5

Hide quick links: