Electrical Work
1. The supply voltage must be the same as the rated
voltage of the air conditioner.
2. Prepare the power source for exclusive use with the
air conditioner.
Model
RAS-B10J2FVG-E
Power source
220–240V ~ 50Hz
Maximum running
6.75A
current
Circuit breaker
10A
rating
H07RN-F or 60245 IEC66
Power cord
(1.5 mm
Connecting cable
When using a multi-system outdoor unit is used,
refer to the installation manual provided with the
model concerned.
Stripping length of the connecting cable
Terminal
block
Connecting cable
Power cord
CAUTION
The power supply must be same as the rated of air conditioner.
1.
Prepare the power source for exclusive use with air conditioner.
2.
Circuit breaker must be used for the power supply line of this air
3.
conditioner.
Be sure to comply power supply and connecting cable for size
4.
and wiring method.
Every wire must be connected firmly.
5.
Perform wiring works so as to allow a general wiring capacity.
6.
Wrong wiring connection may cause some electrical part burn
7.
out.
Incorrect or incomplete wiring is carried out, it will cause an
8.
ignition or smoke.
This product can be connected to main power supply.
9.
Connection to f xed wiring : A switch which disconnects all poles
and has a contact separation at least 3 mm must be
incorporated in the fixed wiring.
RAS-B13J2FVG-E
RAS-B18J2FVG-E
220–240V ~ 50Hz
220–240V ~ 50Hz
7.50A
10.40A
10A
15A
H07RN-F or 60245
IEC66
or more)
2
(2.5 mm
or more)
2
H07RN-F or 60245 IEC66
(1.5 mm
or more)
2
1 2 3
L N
40
30
30
Earth line
Connecting cable
Power cord
10-5. OTHERS
10-5-1. Gas Leak Test
40
10-5-2. Setting of Remote Control
Selector Switch
When two indoor units are installed in the separated
rooms, it is not necessary to change the selector
switches.
Remote control selector switch
• When two indoor units are installed in the same room or adjacent two
rooms, if operating a unit, two units may receive the remote control
signal simultaneously and operate. In this case, the operation can
be preserved by setting either one indoor unit or remote control to B
setting (Both are set to A setting in factory shipment).
• The remote control signal is not received when the settings of indoor
unit and remote control are different.
• There is no relation between A setting/B setting and A room/B room
when connecting the piping and cables.
- 80 -
Check places for flare nut connection
(Indoor unit)
Valve cover
Check the flare nut
connections for the gas
leak with a gas leak
detector or soap water.
Check places for the outdoor unit.