Quick Start Guide
4.11
China
4.11.1 NEPSI Intrinsic Safety (IS)
I3
Summary of product certification
Protection
Certificate
Standards
Markings
Safety
instructions
Special Conditions for Safe Use
1. The 701PBKKF SmartPower Black Power Module (p/n
00753-9220-0001) provided by the manufacturer should be used.
2. The surface resistivity of the polymeric antenna is greater than 1 GΩ.
To avoid electrostatic charge build-up, it shall not be rubbed or
cleaned with solvents or a dry cloth.
3. The Rosemount 2160 enclosure is made of aluminum alloy and given
a protective epoxy coating. However, care should be taken to protect
it from impact or abrasion if located in Zone 0.
4.12
Technical Regulations Customs Union (EAC)
4.12.1 Technical Regulation Customs Union (EAC) Intrinsic Safety (IS)
IM
Summary of product certification
Protection
Certificate
Markings
Special Conditions For Safe Use (X)
See certificate for special conditions
26
Intrinsic Safety (IS)
认证)
GYJ20.1149X
(CCC
GB 3836.1-2010
GB 3836.4-2010
GB 3836.20-2010
Ex ia IIC T5-T2 Ga
See the certificate.
Intrinsic Safety (IS)
RU C-GB.AB72.B.00916
0Ex ia IIC T5...T2 Ga X
Ta (see table in the certificate)