VII. Venting (continued)
WARNING
WARNING
!
DO NOT mix vent systems of
different types or manufacturers.
Failure to comply could result in
severe personal injury, death, or
substantial property damage.
Do NOT connect venting to a
chimney flue that is servicing a
separate appliance designed to
burn solid fuel.
Do not insulate polypropylene vent
pipes. Excessive heat could cause
premature vent pipe failure.
Figure 11: Flexible Vent in Masonry Chimney with Separate Combustion Air Intake
Pressure drop for flexible polypropylene line is 20
% greater than from rigid pipe. Multiply measured
flexible polypropylene liner length by 1.2 to obtain
equivalent length.
Maximum equivalent vent length of flexible
polypropylene liner is 48 ft. (14.6 m).