III. Product Rating, Specifications, and Dimensional Data
AMP Series boilers are condensing, high-efficiency, gas-
fired, hot water boilers designed for use in forced hot
water or heating with indirect domestic hot water heating
systems, where supply water temperature does not exceed
190°F. These boilers have special coil type stainless steel
heat exchangers, constructed, tested and stamped per
Section IV of the ASME Boiler and Pressure Vessel Code,
which provide a maximum heat transfer and simultaneous
protection against flue gas product corrosion. These
Table 1: AMP Boiler Ratings
Input (MBH)
AMP
Boiler Model
Min.
1000
200
1250
250
1500
300
2000
400
2500
500
3000
600
3500
700
4000
800
Ratings shown are for installations at sea level and elevations up to 2000 ft. at minimum vent
1
length. For high altitude installations above 2000 ft. consult factory.
Note: The AMPW hot water supply boiler is rated for 98% thermal efficiency.
Table 2: AMP Specifications
Specification
Fuel
Max. Water Temp.
(°F)
1
Max. Working Pres.
(psi)
Standard Safety
Relief Valve (psi)
2
Water Vol. (gal)
Heat Transfer Area
(sq. ft.)
Approx. Shipping
Weight (lb)
1
Appliance will go into hard lockout if temperature exceeds 200
The standard relief valve pressure rating for all AMPW models is 150 psi.
2
Note: Optional 30, 50, 60, 75, 100, and 125 psi relief valves are available for all AMP Boiler models.
Gross
Output
Max.
(MBH)
1000
970
1250
1213
1500
1455
2000
1940
2500
2425
3000
2910
3500
3395
4000
3880
1000
1250
NG or LP NG or LP NG or LP NG or LP NG or LP NG or LP NG or LP NG or LP
210
210
160
160
50
50
12
12
100
100
922
922
boilers are not designed for use in gravity hot water space
heating systems or systems containing significant amount
of dissolved oxygen (swimming pool water heating, direct
domestic hot water heating, etc.).
This manual also covers the AMP Hot Water Supply Boilers
designed for heating potable water. (AMPW 2500, 3000,
3500, 4000) Information specific to the Dual Gas model
can be found in the appendices.
Thermal
Net Ratings
Efficiency
Water
(MBH)
1
(%)
843
97
1055
97
1265
97
1687
97
2109
97
2530
97
2952
97
3374
97
AMP Boiler Models
1500
2000
2500
210
210
210
160
160
160
50
50
60
13.9
17.2
36.4
120
153
300
1217
1217
2038
F.
0
7
Combustion
Efficiency
(%)
97
97
97
96.9
97
97
97
97
3000
3500
4000
210
210
160
160
60
75
36.4
47.1
47.1
300
403
2038
2485
2485
210
160
75
403