2.1.1
Mount the transmitter in liquid applications
Procedure
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Mount the transmitter so the drain/vent valves are oriented upward.
Figure 2-7: Mounting the Transmitter in Liquid Applications
In-line
2.1.2
Mount the transmitter in gas applications
Procedure
1. Place taps in the top or side of the line.
2. Mount beside or above the taps.
Figure 2-8: Mounting the Transmitter in Gas Applications
In-line
Quick Start Guide
Quick Start Guide
7