Emerson Rosemount 3051 Quick Start Manual page 20

Pressure transmitter, dp flow meter
Hide thumbs Also See for Rosemount 3051:

Advertisement

Quick Start Guide
Standards
Markings
Special Conditions for Safe Use (X):
1. The Rosemount 3051 Wireless Pressure Transmitter shall only be
used with the 701PGNKF Rosemount SmartPower
2. The inline pressure sensor may contain more than 10 percent
aluminum and is considered a potential risk of ignition by impact or
friction. Care must be taken into account during installation and used
to prevent impact and friction.
3. The surface resistivity of the transmitter housing is greater than one
gigaohm. To avoid electrostatic charge build-up, it must not be
rubbed or cleaned with solvents or a dry cloth.
Range 6
Certificate
Standards
Markings
4.5.2
Canada
I6 Canada Intrinsically Safe
Certificate CSA 2526009
Standards CAN/CSA C22.2 No. 0-M91, CAN/CSA C22.2 No.94-M91, CSA
Markings
20
FM Class 3600:2018, FM Class 3610:2018, FM Class
3810:2018, ANSI/ISA 60079-0:2013, ANSI/UL
60079-11:2014, NEMA 250:2003, ANSI/IEC 60529:2014,
ANSI/UL 61010:2016
IS CL I, DIV 1, GP A, B, C, D T4; CL 1, Zone 0 AEx ia IIC T4;
T4(–40 °C ≤ T
a
drawing 03031-1062; Type 4X/IP66/IP68
CSA 2526009
FM Class 3600 - 2011, FM Class 3610 - 2010, FM Class
3810 - 2005, ANSI/ISA 60079-0 - 2009, ANSI/ISA
60079-11 - 2009, UL 61010-1 (3rd edition), UL50E (1st
Edition)
IS CL I, DIV 1, GP A, B, C, D T4; CL 1, Zone 0 AEx ia IIC T4;
T4(-40 °C ≤ T
a
drawing 03031-1063; Type 4X/IP66/IP68
Std C22.2 No. 142-M1987, CSA Std C22.2 No. 157-92, CSA
Std C22.2 No. 60529:05
Intrinsically Safe for Class I, Division 1, Groups A, B, C, D, T4
when installed per Rosemount drawing 03031-1063; Type 4X/
IP66/IP68
≤ +70 °C) when installed per Rosemount
≤ +70 °C) when installed per Rosemount
December 2019
Battery Pack.
Emerson.com/Rosemount