Quick Start Guide
Note
A weep hole has been designed into the transmitter for safety and
leak detection. If fluid begins to leak from the weep hole, isolate the
process pressure, disconnect the transmitter, and reseal until the
leak is resolved.
2.2
Consider housing rotation
To improve field access to wiring or to better view the optional LCD display:
Figure 2-13: Housing Rotation
A. Housing rotation set screw (5/64-in.)
Procedure
1. Loosen the housing rotation set screw using a 5/64-in. hex wrench.
2. Rotate the housing clockwise to the desired location.
3. If the desired location cannot be achieved due to thread limit, rotate
the housing counterclockwise to the desired location (up to 360°
from thread limit).
4. Retighten the housing rotation set screw to no more than 7 in-lb
when it reaches the desired location.
2.3
Connect the power module
Procedure
1. Remove the power module cover.
2. Connect the green power module (see
12
A
December 2019
Figure
2-14).
Emerson.com/Rosemount