8.2

Function modules

Use these modules in slot
Digital frequency
Connections
Pos.
Description
X9
Input for digital frequency, 9-pole Sub-D plug
X10
Output for digital frequency, 9-pole Sub-D socket
X9
5
9
1
6
SUBD09010
EDK94AMH24 DE/EN/FR/ES/IT 1.0
MXI1 or
MXI2
Pin
Designation
Explanation
1
B
2
A
TTL input signal from encoder or encoder simulation
3
A
4
+5 V
Regulated voltage supply for encoder
(pin 8 = sense has to be used)
5
GND
-
6
Z
TTL input signal from encoder or encoder simulation
7
Z
8
The function of this lead has to be set in the standard device:
S
Sense (sensor lead for voltage regulation, Lenze setting)
Lc
Lamp control
E
Enable
9
B
TTL input signal from encoder or encoder simulation
Wiring the device modules
Function modules
MMI
MSI.
8
E94AYFLF004
71