2.6
Combustion chamber pressure
The combustion chamber pressure is the same as for natural
gas.
2.7
Gas pressure and output
measured at the coupling with combu-
Pressure:
stion chamber at 0 mbar. If the combu-
stion
required gas-pressure is that shown on
the diagram plus the pressurization va-
lue.
Example: in order to develop 240 kW it is
necessary to have a 11 mbar at the cou-
pling with the chamber at 0. Should the
combustion chamber be pressurized at
+3 mbar, the required pressure is
11 + 3 = 14 mbar.
maximum output obtainable with:
Output:
–
–
Tab. A indicates the minimum pressure drops along the gas sup-
ply line, depending on the maximum burner output.
chamber
is
pressurized,
gas with a net heat value of 22.200
kcal/m3;
gas ring set as indicated in the Gas
3, Gas 3/2 and Gas 3 P/M technical
instructions under the paragraph
"Combustion - Head Setting".
LPG kit
For pressure levels different from those indicated
above, please contact the Technical Office.
WARNING
Combustion chamber pressure
the
kW
130
154
179
203
228
252
277
301
3
GB
Burner output
1 p (mbar)
G31
5
6,4
7,9
9,3
10,7
12,1
13,6
15,1
D1334
Fig. 2
D1331
Fig. 3
Tab. A
2915326