2.6

Combustion chamber pressure

The combustion chamber pressure is the same as for natural
gas.
2.7
Gas pressure and output
measured at the coupling with combu-
Pressure:
stion chamber at 0 mbar. If the combu-
stion
required gas-pressure is that shown on
the diagram plus the pressurization va-
lue.
Example: in order to develop 1440 kW it
is necessary to have a 17 mbar at the
coupling with the chamber at 0. Should
the combustion chamber be pressurized
at +3 mbar, the required pressure is
17 + 3 = 20 mbar.
maximum output obtainable with:
Output:
Tab. A indicates the minimum pressure drops along the gas sup-
ply line, depending on the maximum burner output.
chamber
is
pressurized,
gas with a net heat value of 22.200
kcal/m3;
gas ring set as indicated in the
Gas 7/2 and Gas 7 P/M technical in-
structions
under
the
paragraph
"Combustion - Head Setting".
LPG kit
For pressure levels different from those indicated
above, please contact the Technical Office.
WARNING
Combustion chamber pressure
the
kW
800
906
1011
1117
1222
1328
1433
1539
3
GB
D1346
Burner output
1 p (mbar)
G31
9.9
11.1
12.3
13.4
14.6
15.8
17,0
18,2
Fig. 2
D1345
Fig. 3
Tab. A
2915329