Combustion Chamber Pressure - Riello GAS 5 Installation, Use And Maintenance Instructions

Lpg kit
Table of Contents

Advertisement

Available languages

Available languages

2.6

Combustion chamber pressure

The combustion chamber pressure is the same as for natural
gas.
2.7
Gas pressure and output
measured at the coupling with combu-
Pressure:
stion chamber at 0 mbar. If the combu-
stion
required gas-pressure is that shown on
the diagram plus the pressurization va-
lue.
Example: in order to develop 450 kW it is
necessary to have a 14 mbar at the cou-
pling with the chamber at 0. Should the
combustion chamber be pressurized at
+2 mbar, the required pressure is
14 + 2 = 16 mbar.
maximum output obtainable with:
Output:
Tab. A indicates the minimum pressure drops along the gas sup-
ply line, depending on the maximum burner output.
chamber
is
pressurized,
gas with a net heat value of 22.200
kcal/m3;
gas ring set as indicated in the
Gas 4, Gas 4/2 and Gas 4 P/M tech-
nical instructions under the para-
graph "Combustion - Head Setting".
LPG kit
For pressure levels different from those indicated
above, please contact the Technical Office.
WARNING
Combustion chamber pressure
the
kW
320
358
396
433
471
509
547
584
3
GB
Burner output
1 p (mbar)
G31
10,0
11,1
12,2
13,4
14,5
15,7
16,9
18,1
D1340
Fig. 2
D1339
Fig. 3
Tab. A
2915327