Air Damper Adjustment - Riello P200 T/G Installation, Use And Maintenance Instructions

Light oil burners
Table of Contents

Advertisement

AIR DAMPER ADJUSTMENT

The air dampers adjustment shall be set each time in relation with the nozzles delivery and the combustion chamber
pressurization.
Fig. 2 shows the placement of the air dampers as fig. 3 their correspondent hydraulic jacks.
To open or close the air dampers proceed as follows:
Loose the ring nut (1), turn clockwise the hexagonal body (2)
in order to decrease the air flow, and counterclocwise to in-
crease it.
The right adjustment of the air dampers may be detect by checking the combustion results in the three stages of
burner operation.
To check the combustion during the different stages, the commutator (see page 10) should be set to the position
corresponding to the burner stage to be controlled.
5906
Fig. 2
st
1
stage air damper
nd
2
stage air damper
rd
3
stage air damper
9
Fig. 3
rd
3
stage hyd. jack
nd
2
stage hyd. jack
st
1
stage hyd. jack

Advertisement

Table of Contents
loading

This manual is also suitable for:

34777853477786

Table of Contents